PLC FAQ's

Answer:

You can extend modules using the existing backplane. When additional backplanes are required, both local I/O extension and remote I/O extension are available. Remote I/O extension is available via DeviceNet. 

System Extension Structure

Answer:

The DVP10MC is a CANopen motion controller and the DVPCOPM-SL is a CANopen master communication module. Both support protocols. The DVP10MC has built-in motion control and PLC functions which adopt the method of CANopen bus to achieve multi-axis motion control. It also supports general extension functions which are the same as the Delta Slim Type extension modules on the left and the PLC on the right. Some default data exchange areas are reserved for data transfer when conducting motion control and program control. 
2. Generate E-CAM data from DTO instructions. 

The CAM chart draws the curves from point-to-point or via functions. 
The DTO instructions automatically create flying shear curves. Users can set relevant parameters and operation requirements for the actual structure of the flying shear. E-CAM curves that meet these requirements can then be created and utilized.

Answer:

There are two ways to create a CAM chart. 
1. Draw E-CAM curves from the CAM chart. 
2. Generate E-CAM data from DTO instructions. 

The CAM chart draws the curves from point-to-point or via functions. 
The DTO instructions automatically create flying shear curves. Users can set relevant parameters and operation requirements for the actual structure of the flying shear. E-CAM curves that meet these requirements can then be created and utilized.

Answer:

Four models do: the EH2-L, 28SV, 12SA2, and 20SX2. 

 

Answer:

The 2-axis 200K models that have such a feature are the 20EH00T2, 32EH00T2, and 32EH00T2-L. The 4-axis 200K model that has this feature is the 40EH00T2.

Answer:

The extension module on the left is a parallel high-speed extension module, that includes extensions to the communication module and analog function. The general extension module is a serial extension module on the right, including extensions to I/O points and analog functions, temperature measurement, motion control, and communication and power modules.

Answer:

The input or output modes of the Delta analog module all have corresponding control register (CR) numbers. The CR data can be read or written using the From/To instructions.

Answer:

The range of analog input voltage for the analog input module DVP04AD/DVP06AD is ± 10V while the range of digital conversion and resolution are ± 8,000 and 14 bits. The range of analog input current is ± 20mA while the range of digital conversion and resolution are ± 4,000 and 13 bits.

Answer:

There are 12 bits of resolution for the analog output module DVP02DA/DVP04DA, a range of 0 ~ 10V for the analog voltage output, and a range of 0 ~20mA for the analog current output. All correspond to the range of 0 to 4,000 for digital data.