HMI FAQ's

Answer:

Yes, it does. It is quite convenient for the users to use.

Answer:

Because the unit of this address is in Word, the address must be 0 or the multiple of 16, i.e. M0, M16, M32, or M48

Answer:

Up to 512 lines can be edited in one macro command. If not enough, the users can write some functions in sub-macro command. The maximum lines that could be edited in one sub-macro command are 512 lines as well.

Answer:

Usually, it is caused by the interference during communication. The users should examine if the whole system is well grounded or not. If the error does not clear and still exists, please try one of the following methods: 
1.If 3.8 inches or 5.7 inches HMI model is used, please ensure that 0V power supply of HMI is well connected to the communication ground (GND) of AC servo drive or AC motor drive. 
2.If 8 inches, 9.4 inches or 10.4 inches HMI model is used, please ensure that the Pin 5 of communication port of HMI is well connected to the communication ground (GND) of AC servo drive or AC motor drive. 

Answer:

The users do not need to rewrite the program files as the screen editor software will automatically adjust the elements in a ratio of equality. It means that the elements in 320 x 240 pixels stored in 5.7 inches model could be adjusted to the elements in 640×48 pixels stored in 10.4 inches model.

Answer:

Up to 512 lines can be edited in one macro command. If not enough, the users can write some functions in sub-macro command. The maximum lines that could be edited in one sub-macro command are 512 lines as well.

Answer:

This is not exactly true. Sometimes, when the baud rate is over high, the controller may not be able to response in real time. When the controller cannot response in real time, it may result in communication retry and slow the communication down.

Answer:

The benefit of the recipe function is that the users do not need to change a lot of parameters manually. When manufacturing more than one product, the recipe function can help to change all of the parameters just one time

Answer:

This problem has already been solved. Both Screen Editor 1.05.83 and later versions (for DOP-A series) and Screen Editor 2.00.17 and later versions (for DOP-B series) support USB DISK mode. The users can use DOP-A series and DOP-B series HMI to upload and download the programs under Windows Vista and Windows 7 without problems.

Answer:

Both Screen Editor 1.05.82 and later version (for DOP-A series) and Screen Editor 2.00.15 and later version (for DOP-B series) support Delta DVP Q-Link controller. Connecting to this controller makes it possible to read all non-consecutive PLC addresses at a time and deliver the command so as to enhance the communication speed efficiently.